NFPA 96, the fire code most Illinois fire departments enforce for commercial kitchens, sets the cleaning schedule by how much grease your kitchen produces. Your fire inspector and your insurance carrier both use it.

Cleaning frequencyType of cooking
MonthlySystems serving solid-fuel cooking: wood-fired ovens, charcoal grills, smokers
QuarterlyHigh-volume cooking: 24-hour restaurants, charbroiling, wok cooking
Every 6 monthsModerate-volume cooking: most full-service and fast-casual restaurants
AnnuallyLow-volume cooking: churches, day camps, seasonal businesses, senior centers

Your schedule can be tighter than the table

The table is the minimum. If an inspection finds grease buildup before your next scheduled cleaning, the system needs to be cleaned then. Kitchens that fry heavily often land on a shorter schedule than their category suggests.

What counts as cleaned

NFPA 96 calls for the whole exhaust system to be cleaned to bare metal: hood, filters, ductwork and the exhaust fan. A cleaning that stops at the hood doesn't meet the code. After each cleaning, a dated certificate goes on the hood showing who did the work and when.